耐火試驗(yàn)中電纜橋架的耐火時(shí)間是如何規(guī)定的?
根據(jù) GB 29415—2013《耐火電纜槽盒》,電纜橋架耐火時(shí)間分為 4 個(gè)等級(jí):
According to GB 29415-2013 "Fire resistant Cable Tray Boxes", the fire resistance time of cable trays is divided into four levels:
F1:大于等于 90 分鐘。
F1: Greater than or equal to 90 minutes.
F2:大于等于 60 分鐘。
F2: Greater than or equal to 60 minutes.
F3:大于等于 45 分鐘。
F3: Greater than or equal to 45 minutes.

F4:大于等于 30 分鐘。
F4: Greater than or equal to 30 minutes.
另外,也有資料將電纜橋架的耐火等級(jí)分為 NI、NII、NIII 三個(gè)等級(jí),其中 NI 等級(jí)耐火時(shí)間大于等于 60 分鐘,NII 等級(jí)大于等于 45 分鐘,NIII 等級(jí)大于等于 30 分鐘。
In addition, there are also materials that classify the fire resistance level of cable trays into three levels: NI, NII, and NIII. Among them, the fire resistance time of NI level is greater than or equal to 60 minutes, NII level is greater than or equal to 45 minutes, and NIII level is greater than or equal to 30 minutes.
不同使用環(huán)境對(duì)防火橋架的耐火時(shí)間要求有所不同,如地下車庫(kù)等對(duì)防火有特別要求的地段,防火橋架耐火時(shí)間要求大于 1 小時(shí)。在實(shí)際應(yīng)用中,應(yīng)根據(jù)具體的工程需求和相關(guān)規(guī)范來(lái)選擇合適耐火時(shí)間的電纜橋架。
The fire resistance time requirements for fire-resistant cable trays vary depending on the usage environment. For example, in underground garages and other areas with special fire protection requirements, the fire resistance time of fire-resistant cable trays should be greater than 1 hour. In practical applications, cable trays with appropriate fire resistance time should be selected based on specific engineering requirements and relevant specifications.
下一篇:耐火試驗(yàn)后電纜橋架的性能和質(zhì)量如何評(píng)估?
相關(guān)文章 / Recommended news
- 山東電纜橋架線槽什么情況下設(shè)置和不設(shè)置跨接線的要求
- 全長(zhǎng)大于30米的電纜橋架,中間增加與保護(hù)導(dǎo)體的連接怎么做?
- 山東電纜橋架的安裝要求
- 濟(jì)南電纜橋架內(nèi)電纜的固定應(yīng)符合相關(guān)標(biāo)準(zhǔn)規(guī)范的規(guī)定
- 地下室山東橋架安裝檢查驗(yàn)收標(biāo)準(zhǔn)、驗(yàn)收節(jié)點(diǎn)
- 濟(jì)南電纜橋架廠家:弱電工程電纜橋架如何施工才規(guī)范?
- 濟(jì)南電纜橋架安裝施工技術(shù)與管控手冊(cè)
- 山東電纜橋架:電力電纜常識(shí)性知識(shí)和電纜試驗(yàn)方法介紹
- 山東電纜橋架安裝施工要求及規(guī)范
- 濟(jì)南電纜橋架安裝施工要求及規(guī)范
濟(jì)南電纜橋架到底需不需要跨接
安裝橋架
安裝橋架
安裝橋架
防火橋架